I have 90 KW motor with soft starter 90 kw installed. How much Kva Generator do i require for the motor?
Dec 28, 2010 by saeed | Posted in Engineering
The running amp of the motor is 133kva.
Limited information means you need to make a few assumptions on power factor and efficiency
Assume PF of 0.75 and efficiency of 90 %
KVA = (KW / Power factor) / efficiency so KVA = (90 / 0.75) / 0.9 = 133.33 KVA